Qualidade ao Seu serviço 

Motor Gen     

 

 Munin
 Approach
 Mission
 Values

 

 Products
 Engines
 Generators (GEs)

 Water pumps

 Parts
 

 Service
 Customer Service
 Warranty

 

 Contacts

 

 

Counter

 


 

 

 

 

 


 
  511.The Genset engine.  

   .........................................................................................................................

         6,8 - 26 kVA at 1500 - 3000 rpm

 
 

         The characteristics of the 511:

 

Naturally aspirated, air cooled,  1cylinder vertical or 2 cylinder in-line engines.

 Displacement: 825 cm3/cylinder

PTO on flywheel and distribution sides.

Compact and powerful.

Advanced injection and combustion system.

Unit construction system with individual cylinders and a maximum of interchangeable parts.

Easy access to all maintenance works.

 

Engine type

 

F1L511

F2L511

Speed

min-1

1500

1800

3000

1500

1800

3000

Frequency

Hz

50

60

50

50

60

50

Engine / genset ratings1)

Continuous power, ICXN (COP)2)

kW

6,1

7,6

11,5

12,2

15,2

23,0

Prime power, ICN (PRP)3)

 

kW

6,4

8,1

12,2

12,8

16,2

24,4

Limited-time running power, IFN (LTP)4)

kW

6,8

8,5

12,8

13,6

17,0

25,7

Typical generator power output (COP)5)

kVA

6,5

8,0

12,2

13,0

16,1

24,4

Typical generator power output (PRP)5)

kVA

6,8

8,6

13,0

13,6

17,2

26,0

Typical generator power output (LTP)5)

kVA

7,2

9,0

13,6

14,5

18,1

27,3

Weight

kg

1366)

1756)

 

1)       Possible power reduction depending on altitude and temperature. Every 5ºC above standard reference temperature: 5% power loss. Every 100m additional altitude above standard reference (100m above sea level): 2,5% power loss.

2)       Continuous power 100% available at flywheel, no time limitation, plus 10% extra power for governing purposes.

3)       Prime power 100%, mean power output 60%, no time limitation, plus 5% extra power for governing purposes.

4)        Limited-time running power 100%, which must be available during 500 running hrs/year, thereof max. 300 running hrs/year continuously, no overload permissible; the required extra power for governing purposes must be taken in account however.

5)        Taking into account typical generator efficiency of 85% and power factor cos (j) = 0,8.

6)        Depending on the version.